介绍了中性点不接地系统的特点,基于电容电流、消弧线圈容量、脱谐度、中性点位移电压的计算公式,开发了变压器并列运行计算分析软件。以A变电站为例,计算和确定了35 kV消弧线圈档位,可供实际工作参考。
This paper introduces the characteristics of ungrounded neutral system,and develops a calculation and analysis software for parallel operation of transformer based on calculation formulas of capacitance current,arc suppression coil capacity,detuning degree and neutral displacement voltage.With substation A as an example,the tap position of 35 kV arc suppression coil is calculated and determined,which has guiding significance for practical work.
作者
阳丽
YANG Li(Laibin Power Supply Bureau of Guangxi Power Grid Co.,Ltd.,Laibin 546100,China)
出处
《电工技术》
2020年第11期104-106,113,共4页
Electric Engineering
关键词
不接地系统
电容电流
消弧线圈
档位
ungrounded system
capacitive current
arc suppression coil
tap position