期刊文献+

机组水汽氢电导率间断超标原因分析及解决措施 被引量:1

Cause Analysis on Unit Water Vapor Hydrogen Conductivity Interruption Exceeding Standard and Settlements
下载PDF
导出
摘要 针对某机组水汽氢电导率间断超标的问题进行分析判断,认为水汽系统总有机碳(TOC)高是导致该机组水汽氢电导率超标的主要原因,现有补给水处理系统与机组实际需求不匹配是机组水汽氢电导率超标的直接原因,并提出了解决水汽超标的具体措施。 Moisture in hydrogen electric conductivity of a unit continuously excessive amounts of problem are analyzed,among them,the water vapor system total organic carbon(TOC)is the unit of the main causes of excess moisture in hydrogen electric conductivity,the existing supply water treatment system and the actual demand does not match the crew is the immediate cause of excess moisture in hydrogen electric conductivity of unit,and puts forward the concrete measures to solve the excess moisture.
作者 张宝军 ZHANG Baojun(Datang Northeast Electric Power Test&Research Institute Co.,Ltd,Changchun 130000,China)
出处 《河北电力技术》 2020年第3期44-46,共3页 Hebei Electric Power
关键词 氢电导率 总有机碳 阴离子 hydrogen conductivity total organic carbon anion