摘要
分析了造成就地化分布式子机保护动作行为不一致的原因,以及子机中断机制对保护计算的影响。各子机间中断异步将导致保护离散采样、数据插值、积分计算的一系列差异,进而导致保护动作行为不一致。针对子机中断异步问题,着重介绍了就地化分布式保护子机中断同步方法,方法不依赖于外部对时源,能够在较短时间内完成各子机同步。分析计算结果表明,子机中断同步后各子机能够有效降低保护计算值差异,进而增强保护动作行为的一致性。文中同时介绍了子机中断同步在异常情形下的处理方法。
The reasons for the inconsistency of action behavior of on-site distributed sub-unit protection and the influence of subunit interrupt mechanism on protection calculation are analyzed. The interrupt asynchrony among sub-units will lead to a series of differences in discrete sampling, data interpolation and integral calculation of the protection, which will further lead to inconsistent protection action behavior. To solve the interrupt asynchronous problem of sub-units, this paper focuses on the interrupt synchronous method for the on-site distributed protection sub-units. This method does not depend on the external time source and can complete the synchronization of sub-units in relatively shorter time. The analysis and calculation results show that the difference in protection calculation values can be effectively reduced after the interrupt synchronization of sub-units, then the consistency of protection action behavior is enhanced. The processing method for the sub-unit interrupt synchronization is also introduced in abnormal circumstances.
作者
顾乔根
周华
许宗光
龚啸
汪冬辉
顾浩
GU Qiaogen;ZHOU Hua;XU Zongguang;GONG Xiao;WANG Donghui;GU Hao(NR Electric Co.,Ltd.,Nanjing 211102,China;NARI Group Corporation(State Grid Electric Power Research Institute),Nanjing 211106,China;State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310007,China;Electric Power Research Institute of State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310014,China)
出处
《电力系统自动化》
EI
CSCD
北大核心
2020年第16期178-183,共6页
Automation of Electric Power Systems
基金
国家电网公司科技项目(521104180017)。
关键词
就地化保护
分布式子机
中断同步
保护动作
动作行为
on-site protection
distributed sub-unit
interrupt synchronization
protection action
action behavior