期刊文献+

不同末端形式下双冷源辐射空调系统模拟研究

Simulation Study of Dual Cold Source Radiant Air Conditioning System with Different Terminals
下载PDF
导出
摘要 本文采用EnergyPlus能耗模拟软件,以上海市某别墅为建筑对象,对顶板/墙面辐射+置换通风两种不同双冷源空调系统进行设计工况下的热舒适和能耗模拟分析,同时与VRV空调系统的模拟结果进行对比。结果表明:与VRV系统相比,墙面辐射双冷源空调系统具有更好的热舒适性、更低的能耗。达到相同的热舒适度标准,所用时间更少。全年供冷主机能耗可节约50%,供热主机能耗可节约23%。 Using EnergyPlus energy simulation software,a villa in Shanghai was taken as an example.The thermal comfort and energy consumption of the roof/wall capillary radiation+displacement ventilation with dual cold source air-conditioning systems are analyzed under the design conditions,while the VRV air conditioning system is served as a simulation reference.The simulation results show that compared with the VRV system,the wall-radiation dual-cold source air-conditioning system has better thermal comfort and lower energy consumption;toward the same thermal comfort standard can save a lot of time;The energy consumption of the cooling plant can be saved by 50%,and the energy consumption of the heating plant can be saved by 23%.
作者 刘建峰 梁珍 LIU Jian-feng;LIANG Zhen(School of Environmental Science and Engineering,Donghua University)
出处 《建筑热能通风空调》 2020年第6期27-31,共5页 Building Energy & Environment
关键词 ENERGYPLUS 双冷源 辐射末端 热舒适性 能耗 EnergyPlus dual cold source radiation terminal thermal comfort energy consumption
  • 相关文献

参考文献4

二级参考文献25

  • 1赵鑫,刘轶.变风量空调系统在别墅中的应用[J].暖通空调,2005,35(9):85-88. 被引量:2
  • 2陆耀庆.实用供热空调设计手册[M].2版.北京:中国建筑工业出版社,2007.
  • 3Jeong J W, Mumma S A, Bahnfleth W P. Energy conservation benefits of a dedicated outdoor air system with parallel sensible cooling by ceiling radiant panels [J]. ASHRAE Transaction, 2003,109 (2) : 627-636.
  • 4Catalina T, Virgone J, Kuznik F. Evaluation of thermal comfort using combined CFD and experimentation study in a test room equipped with a cooling ceiling [J]. Building and Environment, 2009,44 : 1740-1750.
  • 5Vangtook P, Chirarattananon S. An experimental investigation of application of radiant cooling in hot humid climate[J]. Energy and Building, 2006,38 : 273- 285.
  • 6Lim J H, Jo J H, Kim Y K, et al. Application of the control methods for radiant floor cooling system in residential buildings [J]. Building and Environment, 2006,41:60-73.
  • 7Mumma S A, Jeong J W. Direct digital temperature, humidity, and condensate control for a dedicated outdoor air-ceiling radiant cooling panel system [J]. ASHRAE Transaction,2005,111(part 1) :547-558.
  • 8Xuan Y M, Huang X, Kang N, et al. Experimental study of a hybrid radiant cooling air conditioning system based on evaporative cooling used in Xi'an city, China [C]//The 7th International Symposium on Heating,Ventilation and Air Conditioning. Shanghai: Tongji University: 27-32.
  • 9闰振华.基于蒸发冷却辐射供冷/热空调系统实验研究[D].西安:西安工程大学,2008.
  • 10Novoselac A, Srebric J. A critical review on the performance and design of combined cooled ceiling and displacement ventilation systems [J]. Energy and Buildings, 2002, 34: 497-509.

共引文献26

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部