1100kV GIL产品现场试验研究 被引量:1

Study on Field Test of 1100 kV GIL Product
下载PDF
导出
摘要 1100 kV气体绝缘金属封闭输电线路(GIL)设备为世界范围内较先应用,目前尚无完善的现场交接试验方案,为解决这一现状,对制约1100 kV GIL现场交接试验的项目进行了分析研究。通过创新现场主电阻和气体密度测量方法,将常规电阻测试中的正极或负极电流测试线用1100 kV GIL外壳代替,并设计专门的电阻测量结构,解决了现场测试线长度不足的难题;通过制作专门的硬质检漏工装,解决了现场检漏气体定量不准确的问题。该方案的实施,解决了困扰1100 kV GIL现场交接试验的困难。 The 1100 kV GIL is the first application in the world.At present,there is no perfect on-site handover test scheme.In order to solve the problem,the project that restricts the 1100 kV GIL field handover test was analyzed and researched.By innovating on-site main resistance and gas density measurement methods,replacing the positive or negative current test line in the conventional resistance test with a 1100 kV GIL shell,and designing a special resistance measurement structure to solve the problem of insufficient field test line length.The problem of inaccurate gas quantification for on-site leak detection is solved though making special hard leak detection tooling.The implementation of this program solved the difficulties that plagued the 1100 kV GIL field handover test.
作者 孙琼 许罗生 包联霜 SUN Qiong;XU Luo-sheng;BAO Lian-shuang(Pinggao Group Co.,Ltd,Pingdingshan 467001,China)
出处 《电工电气》 2020年第9期43-46,共4页 Electrotechnics Electric
关键词 气体绝缘金属封闭输电线路(GIL) 试验方案 现场试验 管廊 GIL test scheme field test pipe corridor