与220 kV单层构架出线不同,双层构架采用常规终端塔出线,将导致大部分相序排列组合的导线相间距离不满足规范要求,成为变电站布置双层构架的制约因素。通过采用三维坐标转换方法,编制进线档相间距离简易计算程序。针对220kV双层构架采用常规终端塔出线相序适用率低的问题,提出适用于错层终端塔的解决方案,提高了双层构架出线相序排列的自由度。
Different from the outgoing line schemes of single-layer framework,the double-layer framework with the conventional terminal tower outlet will result in the phase-to-phase distance of most phase sequence combinations not meeting the specification requirements.It becomes a constraint factor for the promotion of double layer framework.According to the 3D space transformation technology,the paper has compiled a simple calculation program for the phase distance of lead-in span.Aiming at the problem that the double-layer framework with the conventional terminal tower outlet adopts the low rate of the phase sequence,the solution of the staggered-layer terminal tower is proposed,and the degree of freedom of the phase sequence arrangement is improved.
作者
包华
杨超
张大伟
鲍松
张君宇
BAO Hua;YANG Chao;ZHANG Da-wei;BAO Song;ZHANG Jun-yu(Anhui Electric Power Design Institute Co.,Ltd.of CEEC,Hefei 230601,China)
出处
《电力勘测设计》
2020年第9期60-65,共6页
Electric Power Survey & Design
关键词
双层构架
出线方式
相间距离
相序排列方式
错层终端塔
double layer framework
phase-to-phase distance
phase sequence arrangement