摘要
文章介绍了主变差动保护异常跳闸现象。对可能影响主变差动保护动作跳闸条件进行了梳理,结合微机主变差动保护躲励磁涌流的常用措施,找出了该主变差动保护A套动作跳闸及B套保护闭锁不动作的原因。结合现场检查处理情况针对本次主变两套差动保护跳闸不一致的原因提出了整改的措施,避免类似故障再次发生。
This paper introduces the abnormal tripping of the differential protection of main transformer and discusses the tripping conditions that may affect the differential protection of main transformer.Considering the common measures of the differential protection of main transformer to avoid the inrush current of excitation,the paper finds out the reason why the A set of differential protection trips but the B set of differential protection does not.Based on the on-site inspection and treatment,it puts forward corrective measures against inconsistent tripping to prevent similar faults from happening again.
作者
徐建友
赵勇呓
赵创业
XU Jianyou;ZHAO Yongyi;ZHAO Chuangye(State Grid Huaibei Power Supply Company,Huaibei 235000,China)
出处
《安徽电气工程职业技术学院学报》
2020年第3期29-34,共6页
Journal of Anhui Electrical Engineering Professional Technique College
关键词
差动保护
涌流
二次谐波
虚回路
differential protection
inrush current
second harmonic
virtual circuit