期刊文献+

一起110 kV CVT介损和电容量超标故障分析

Analysis of a 110 kV CVT Dielectric Loss and Capacitance Exceeding Standard Fault
下载PDF
导出
摘要 描述了一起110 kV变电站电容式电压互感器介损和电容量超标故障案例,通过CVT自激法试验对电容分压器的主电容和分压电容分别测试了介损和电容量,对数据异常的B相CVT进行了解体检查和绝缘油化验分析,找到了该起故障原因,提出了及时发现诊断CVT故障的措施和建议。 A case of over standard dielectric loss and capacitance of capacitor voltage transformer in 110 kV substation was introduced.Through the CVT self-excitation method test,the dielectric loss and capacitance of the main capacitor and the voltage dividing capacitor of the capacitor voltage divider were tested respectively.The cause of the fault was found by physical examination and insulating oil analysis of B-phase CVT with abnormal data.The measures and suggestions for finding and diagnosing CVT fault in time were put forward.
作者 谭湘海 唐颖凯 刘海龙 张芳 TAN Xianghai;TANG Yingkai;LIU Hailong;ZHANG Fang(State Grid Hunan Xiangtan Power Supply Company,Xiangtan 411104,China)
出处 《电工技术》 2020年第18期90-92,共3页 Electric Engineering
关键词 电容式电压互感器 介损 电容量 解体检查 油化验分析 capacitive voltage transformer dielectric loss capacitance disintegration inspection oil analysis