广州地铁14号线嘉禾望岗站空调冷却水系统能效分析 被引量:7

Energy efficiency analysis of air conditioning cooling water system in Jiahe Wanggang Station of Guangzhou underground railway line 14
下载PDF
导出
摘要 以广州地铁14号线嘉禾望岗站空调冷却水系统为研究对象,建立了基于实验室数据拟合的系统能效模型。以运行能效为优化指标,对比分析了不同负荷率及湿球温度下不同冷却水量和冷却风量时的冷却水系统能效理论计算值,得到了最佳运行风水比。实际运行数据表明,运行该优化控制策略,可以获得较高的冷却水系统能效,但仍需对部分工况下的冷却水系统能效模型进行修正。 Taking the cooling water system of Jiahe Wanggang Station.of Guangzhou underground railway line 14 as a research object,establishes a fited system energy efficiency model based on laboratory data.Taking the operation energy efficiency as the optimization index,analyses and compares the theoretical calculation values of cooling water system energy efficiency at different load rates and wet-bulb temperatures with different cooling water flow and cooling air rates,and obtains the optimal operation air-water ratio.The actual operation data show that the optimal control strategy can result in higher cooling water system energy efficiency,but the cooling water system energy efficiency model still needs to be modified under some conditions.
作者 刘昶 吴疆 张瑞 王绍兴 沈智广 张光斌 翁李帅 沈岑 郁辉球 Liu Chang;Wu Jiang;Zhang Rui;Wang Shaoxing;Shen Zhiguang;Zhang Guangbin;Weng Lishuai;Shen Cen;Yu Huiqiu(Guangzhou Metro Group Co.,Ltd.,Guangzhou,China;不详)
出处 《暖通空调》 2020年第10期76-81,共6页 Heating Ventilating & Air Conditioning
基金 广州市轨道交通14号线地下车站高效环控系统建设与能效保持关键技术研究项目(编号:18A0005)。
关键词 冷却水系统 负荷率 湿球温度 冷却水量 冷却风量 风水比 能效 cooling water system load rate wet-bulb temperature cooling water rate cooling air rate air-water ratio energy efficiency
  • 相关文献

参考文献6

二级参考文献41

  • 1吴挺,郁文红.对集中空调冷却水系统变流量的思考[J].暖通空调,2004,34(12):37-38. 被引量:6
  • 2周洪煜,徐春霞,陈晓锋,王驹.集中空调水系统的变流量节能改造[J].重庆大学学报(自然科学版),2006,29(12):41-44. 被引量:5
  • 3黄建恩,冯伟.一种螺杆式制冷机组能耗计算模型[J].暖通空调,2007,37(4):121-126. 被引量:4
  • 4周金鑫,陈卫,陈瑞.集中空调系统冷却塔的运行管理与节能[J].暖通空调,2007,37(7):142-144. 被引量:6
  • 5BAHNFLETH W P, PEYER E. Comparative analysis of variable and constant primary flow chilled water- plant performance[J]. Heating, Piping, Air Conditioning Engineering, 2001,73 (4) :41-50.
  • 6JIN X, DU Z. Energy evaluation of optimal control strategies for central VWV chiller systems[J]. Applied Thermal Engineering, 2007,27(5/6): 934- 941.
  • 7CHANG Y C, CHEN W H. Optimal chilled water temperature calculation of multiple chiller systems using Hopfield neural network for saving energy[J]. Energy, 2009,34(4): 448-456.
  • 8CHANG Y C. Application of hopfield neural network to the optimal chilled water supply temperature calculation of air conditioning systems for saving energy[J]. International Journal of Thermal Sciences, 2009,48(8):1649-1657.
  • 9ZHEN J, WANG S W. Energy efficient control of variable speed pumps in complex building central airconditioning systems[J]. Energy and Buildings, 2009, 41(2):197- 205.
  • 10GORDON J M, NG K C,CHUA H T. How varying condenser coolant flow rate affects chiller performance.. thermodynamic modeling and experimental confirmatlon[J]. Applied Thermal Engineering, 2000, 20 (13) :1149-1159.

共引文献85

同被引文献47

引证文献7

二级引证文献10

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部