污水泵站集水池有效容积的分析与探讨

Analysis and Discussion of Effective Volume of Wastewater Collection Tank in Sewage Pumping Station
下载PDF
导出
摘要 污水泵站集水池调节容积过大,将会增加工程造价;调节容积过小,将会造成水泵的频繁启停,缩短水泵使用寿命。为了得出合理的集水池容积,根据《室外排水设计规范》(GB 50014—2006)中每小时水泵开动不得超过6次的要求,结合不同的水泵台数和2种水泵启停方案,采用数学建模的方法,对污水泵站集水池容积进行了分析与探讨。结果表明,不同水泵台数及启停方案,集水池容积要求不同,且随着水泵台数的增加,规范要求的最小容积将低于水泵6次/h运行所需的调节容积要求。 A large regulating capacity of sump in sewage pumping station will increase project cost.A small regulating capacity will make the pump frequent start and stop,shorten service life of the pump.In order to obtain optimum volume of wastewater collection tank,according to requirement of Code for Design of Outdoor Wastewater Engineering(GB 50014—2006)that one pump must start on less than 6 times per hour,combined with different number and two pump on-off schemes,volume of wastewater collection tank in sewage pumping station is analyzed and discussed with the method of mathematical modeling.Results show that the volume requirements of collection tank are different under different number of pumps and pump on-off schemes,and with the increase of the number of pumps,minimum volume value required by code may be lower the regulated volume required for 6 pump runs per hour.
作者 陈喆 CHEN Zhe(Shanghai Municipal Engineering Design General Institute,Shanghai 200092,China)
出处 《净水技术》 CAS 2020年第10期29-36,48,共9页 Water Purification Technology
基金 国家重点研发计划资助(2018YFC0704800)。
关键词 污水泵站 启停方案 集水池容积 sewage pumping station on-off operation scheme volume of wastewater collection tank
  • 相关文献

参考文献2

二级参考文献6

  • 1于卫红.城市排水规划的热点问题探讨[J].中国给水排水,2006,22(8):16-18. 被引量:14
  • 2盛建康,邓培德,毛孟修,等.GB/T50014-2006室外排水设计规范[S].北京:中国计划出版社,2006.
  • 3北京市市政工程设计研究总院.给排水设计手册:城镇排水[M].2版.北京:中国建筑工业出版社,2004:169-170.
  • 4窦以松,刘清奎,陈登毅,等.GB/T50265-97泵站设计规范[S].北京:中国计划出版社,1997.
  • 5GB/T50265-97.泵站设计规范[S].[S].,..
  • 6GB 50014-2006,室外排水设计规范[S].

共引文献28

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部