期刊文献+

除氧器供汽逆止阀卡涩引发锅炉MFT 被引量:1

MFT of Boiler caused by Jamming of Deaerator Steam Supply Check Valve
原文传递
导出
摘要 针对机组RB试验期间,给水流量低引发锅炉MFT的过程进行了详细的介绍,指出除氧器供汽逆止门卡涩,除氧器内大量饱和水闪蒸,返流至小机供汽管路,是导致汽动给水泵出力下降,给水流量降低的主要原因。建议更换除氧器供汽逆止阀并修改除氧器电动门逻辑,以避免该类事故发生的。 The process of boiler MFT caused by too low feed water flow during the runback test of the unit is introduced in detail.It is pointed out that the main reason for the decrease of feed water flow is that the steam supply check valve of deaerator is jammed,a large amount of saturated water in deaerator is evaporated and flows back to the steam supply pipeline of feed pump turbine.It is recommended to replace the steam supply check valve of deaerator and modify the logic of deaerator electric valve to avoid such accidents.
作者 张鹏 ZHAGN Peng(Xi'an Branch of North China Electric Power Research Institute Co.,Ltd.)
出处 《电站系统工程》 2020年第6期33-34,共2页 Power System Engineering
关键词 除氧器 逆止阀 卡涩 MFT deaerator check valve jam boiler MFT
  • 相关文献

参考文献5

二级参考文献4

共引文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部