期刊文献+

ZLS-3300制冷装置在井下集中降温系统中的应用 被引量:1

Application of ZLS-3300 refrigeration device in centralized cooling system in underground mine
原文传递
导出
摘要 为有效解决大采深矿井和大型机械化矿井的高温热害问题,从制冷装置设计加工、需冷量计算、降温系统工艺设计、主要设备选型配套等方面进行系统研究,有针对性地提出了解决矿井高温热害的方案。根据ZLS-3300制冷装置制冷量大、承压高、结构紧凑的优点,将其推广应用在霄云煤矿井下集中制冷降温系统中,并考察应用效果。应用实践表明,采掘工作面降温降湿效果显著,降温后工作面平均干球温度不超过26℃,平均相对湿度不超过70%;回风口干球温度不超过28℃,相对湿度不超过80%,达到了规定的指标要求。 In order to effectively solve the problem of high-temperature thermal damage in large mining deep mines and large mechanized mines,a systematic study was carried out from the design and manufacture of refrigeration devices,calculation of cooling capacity,process design of cooling system,model selection and matching of main equipments etc.,and a targeted scheme was put forward to solve the high-temperature thermal damage in mines.According to the advantages of ZLS-3300 refrigeration device such as large cooling capacity,high pressure-carrying ability and compact structure,it was applied in the underground centralized cooling system of Xiaoyun Colliery.The application showed:the temperature and humidity of the working face significantly reduced,the average dry bulb temperature of the working face was below 26℃and the average relative humidity was below 70%;at the return air port,the dry bulb temperature was below 28℃and the relative humidity was below 80%,which met the requirements of relevant regulations.
作者 张习军 ZHANG Xijun(National Key Laboratory of Gas Disaster Detecting,Preventing&Emergency Controlling,Chongqing 400037,China;Chongqing Research Institute,China Coal Technology&Engineering Group,Chongqing400037,China)
出处 《矿山机械》 2020年第10期62-65,共4页 Mining & Processing Equipment
关键词 制冷装置 井下集中降温 需冷量 refrigeration device centralized cooling in underground mine cooling capacity
  • 相关文献

参考文献3

二级参考文献12

共引文献22

同被引文献8

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部