摘要 介绍了一起500 kV变压器在空载合闸时重瓦斯保护动作的经过,通过对现场情况和设备信息故障录播进行检查,对事件原因进行排查,找到真正原因。保护之所以动作是由于变压器瓦斯继电器在励磁涌流产生的变压器震动和油流涌动导致了误动,并提出了具体的整改措施。 This article introduces the action process of the heavy gas protection under no-load closing condition of the 500 kV transformer,the on-site condition and equipment fault information recordings are examined to investigate the cause of event,and finally the exact cause is found,the transformer vibration due to magnetizing inrush current and oil flow surge may have caused false operation of transformer gas protection relay.The paper puts forward specific improvement measures.
作者 张兴飞 ZHANG Xingfei(Maintace Company of State Grid Hebei Electric Power Co.,Ltd.,Shijiazhuang 050071)
出处 《电力安全技术》 2020年第11期67-70,共4页 Electric Safety Technology
关键词 变压器 瓦斯继电器 励磁涌流 油流涌动 transformer gas relay magnetizing inrush oil flow surge