摘要
针对民用建筑中最常见的低压配电系统设计,通过对最不利情况的电缆短路热稳定校验分析和保护电器的限流特性,推论低压配电屏馈电回路电缆规格的设计选择通常是以导体的载流量满足保护电器过负荷保护为主要决定因素,而可忽略其短路热稳定的校验要求。
In allusion to the design of the most common low‑voltage power distribution system in civil buildings,the short‑circuit thermal stability verification analysis is carried out for the cables under the most unfavorable cases.It is inferred,due to the current limiting characteristics of the protective electrical appliances,that the main decisive factor for designing and selecting the specifications of the feeder cables used for the low‑voltage power distribution panel is as follows:the current carrying capacity of the conductor meets the overload protection of protective electrical appliances,while the verification requirements for short‑circuit thermal stability can be ignored.
作者
李金林
LI Jinlin(Guangdong Boyi Architectural Design Institute Co.,Ltd.,Foshan 528311,Guangdong Province,China)
出处
《建筑电气》
2020年第12期66-69,共4页
Building Electricity
关键词
民用建筑
低压配电
短路
电缆
载流量
热稳定校验
塑壳断路器
过负荷保护
civil buildings
low‑voltage distribution
short‑circuit
cable
current‑carrying capacity
thermal stability verification
molded‑case circuit breaker
overload protection