期刊文献+

飞摆过速装置故障导致轴电流保护动作事故分析与处理

Analysis of Shaft Current Protection Operation Caused by Centrifugal Pendulum
下载PDF
导出
摘要 抽蓄机组轴电流保护动作原因较为复杂,因飞摆过速装置导致轴电流保护动作尚属首次。介绍了一起抽蓄机组轴电流保护动作的事故,通过分析排查,确定故障原因为飞摆过速装置万向轴与过速装置本体连接处锁紧顶丝松动,造成万向轴下沉并与飞摆过速装置底座发生摩擦接地。介绍事故处理过程,提出了防控措施,对同类型机组运行维护工作具有借鉴意义。 The reason of shaft current protection action of pumped storage unit is more complex,and it is the first time that the shaft current protection operation is caused by centrifugal pendulumAn accident of shaft current protection operation of the pumping and storage unit was introduced.Through analysis,it is determined that the cause of the fault is that the locking screw and the cardan shaft sinks and rubs against the base of centrifugal pendulum.The process of accident treatment and puts forward the prevention and control measures were introduced,which can be used for reference for the operation and maintenance of the same type of units.
作者 张婷 刘福春 许准 Zhang Ting;Liu Fuchun;Xu Zhun(Beijing Shisanling Pumped Storage Power Station,State Grid Xinyuan Co.,Ltd.,Beijing 102200,China)
出处 《机电工程技术》 2020年第12期212-213,220,共3页 Mechanical & Electrical Engineering Technology
关键词 轴电流保护 发电机轴接地 离心飞摆装置 shaft current protection generator shaft grounding centrifugal pendulum
  • 相关文献

参考文献10

二级参考文献18

共引文献29

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部