南宁某动车检修库夏季热环境实测与分析 被引量:3

Field Measurement and Analysis of Thermal Environment in the Train Service Shop
下载PDF
导出
摘要 针对我国南方地区动车检修库夏季室内热环境问题,以南宁某动车检修库为研究对象,对室内热环境进行现场实测与调研,通过对测试结果的分析,得出该动车检修库垂直高度方向上温度出现明显的分层现象,二、三层作业平台间的平均温差在1.6℃左右,且在12:00~17:00间主要工作区域的温度均超过35℃;在横轴方向上,温度出现对称分布,中间区域的温度明显高于两侧;与温度不同,相对湿度与空间位置没有明显关系,且二者随时间的变化规律并不同步,温度最高时相对湿度最低,反之亦然,在0:00~11:00间平均相对湿度最大,为72%。所得到的温湿度数据及分布规律为该动车检修库的通风系统设计和改善提供了参考依据。 Aiming at the indoor thermal environment problem of the train service shop in the south of China in summer,a certain train service shop is taken as the research object,and the indoor thermal environment is measured and investigated on the spot.Through analysis of the test results,in the vertical height direction there is significant temperature stratification.The mean temperature difference between the second and third working platforms is about 1.6℃,and the temperature in the main working area is more than 35℃between 12:00 and 17:00.In the horizontal axis direction,there is a symmetrical temperature distribution,and the temperature in the middle area is significantly higher than both sides.Unlike temperature,relative humidity has no obvious relationship with spatial location.The relative humidity is the lowest when the temperature is the highest,and vice versa.
作者 陈思 余南阳 Chen Si;Yu Nanyang(SouthwestJiaotong University,Chengdu,610031)
机构地区 西南交通大学
出处 《制冷与空调(四川)》 2020年第6期707-710,共4页 Refrigeration and Air Conditioning
关键词 动车检修库 现场实测 温度分层 热湿环境 train service shop indoor comfort field measurement temperature stratification
  • 相关文献

参考文献4

二级参考文献13

  • 1李晓冬,岳峻岷,陆亚俊,王丽娜.地下车库中诱导通风方式的数值模拟[J].哈尔滨商业大学学报(自然科学版),2003,19(5):603-606. 被引量:13
  • 2蔡浩,朱培根,谭洪卫,王恩丞,龙惟定.地下车库诱导通风系统的数值模拟与优化[J].流体机械,2004,32(12):27-30. 被引量:13
  • 3Launder B E,Spalding D B.The numerical computation of turbulence flows[J].Computing Methods Applied Mechanical Engineering,1974(3):269
  • 4Xu Weiran.New turbulence models for indoor air flow simulation[D].USA:Massachusetts Institute of Technology,1998
  • 5Chen Qingyan,Xu Weiran.A zero-equation turbulence model for indoor air flow simulation[J].Energy and Buildings,1998,28(2):137-144
  • 6Zhao Bin,Li Xianting,Yan Qisen.A simplified system for indoor airflow simulation[J].Building and Environment,2003,38(4):543-552
  • 7Zhao Bin,Li Xianting,Yan Qisen.Numerical simulation of air distribution in chair ventilated room by simplified methodology[G]//ASHRAE Trans,2002,108(2):1079-1083
  • 8Fluent Inc.Airpak 2.0 Users Guide.Fluent Inc,2001
  • 9胡朋志,郭玉霞.浅谈地下式地铁车辆段总平面布置的特点[J].科技信息(科学教研),2008,(19):381-382.
  • 10Sandberg M, Sj?berg M. The use of moments for assessing air qu -ality in ventilated rooms[J]. Building& Environment, 1983, 18 (83): 181-197.

共引文献9

同被引文献14

引证文献3

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部