期刊文献+

基于带电监测的配网避雷器联合状态诊断研究

Research on Joint Condition Diagnosis of Arrester in Distribution Network Based on Live-line Monitoring
下载PDF
导出
摘要 针对常见的配网避雷器,对其性能及常见故障进行了分析,提出了基于带电监测的3种联合状态诊断方法,通过实际现场案例对配网避雷器进行了运行电压下交流泄漏电流、红外测温以及在线监测数据的综合试验分析,并结合停电试验数据进一步验证,证实了基于带电监测的配网避雷器联合诊断方法能够及时发现避雷器内部绝缘缺陷。 Based on the analysis of the performance and common faults in the distribution network arresters,three joint state diagnosis methods based on live-line monitoring were proposed.In the actual case,the comprehensive test and analysis of AC leakage current under the operating voltage,infrared temperature measurement,on-line monitoring data were carried out.Combined with the test data of power failure,the further verification was carried out.It is proved that the joint state diagnosis methods of arrester in distribution network based on live-line monitoring can find the internal insulation defects of the arrester in time.
作者 张诣 代正元 方勇 王清波 邹璟 ZHANG Yi;DAI Zhengyuan;FANG Yong;WANG Qingbo;ZOU Jing(Kunming Power Supply Bureau,Yunnan Power Grid Co.,Ltd.,Kunming 650011,China)
出处 《现代建筑电气》 2020年第12期18-22,共5页 Modern Architecture Electric
关键词 配网避雷器 带电监测 联合状态诊断 解体分析 distribution network arrester live-line monitoring joint condition diagnosis disintegration analysis
  • 相关文献

参考文献6

二级参考文献39

  • 1郭红英,石芳,郭强,郭炜,赵果萍.避雷器在线监测系统应用[J].电力学报,2004,19(1):72-73. 被引量:15
  • 2谢鹏,张国栋.金属氧化物避雷器试验测试方法的发展及应用[J].电瓷避雷器,2006(5):36-38. 被引量:54
  • 3陈化刚.电力设备异常运行及事故处理[M].北京:中国水利电力出版社,1999.
  • 4DL/T393--2010.输变电设备状态检修试验规程[S].
  • 5Q/CSG114002-2011,电力设备预防性试验规程[S].
  • 6DL/T596-1996.电力设备预防性试验规程[S].[S].,..
  • 7Q/CSGll4002-2011电力设备预防性试验规程[S].
  • 8GB 50150-2006电力装置安装工程电气设备交接试验标准[S].
  • 9李建明;朱康.高压电气设备试验方法[M]{H}北京:中国电力出版社,2001.
  • 10陈化钢.电气设备预防性试验方法及诊断技术[M]{H}北京:中国水利水电出版社,2009.