500 kV GIS断路器单相接地故障分析和处理 被引量:1

Analysis and Treatment of a Single-phase Grounding Fault in 500 kV GIS Circuit Breaker
下载PDF
导出
摘要 基于某大型水电站500 kV GIS开关站1台发变组出口断路器在分闸状态发生单相接地故障,造成该断路器所在联合单元进线串短线差动保护动作,1台运行机组从系统解列。通过对保护故障录波、故障范围SF6隔室气体成分分析和故障断路器解体检查,明确了故障原因,通过更换断路器解决了故障。经对故障原因进行深入探讨,提出了有针对性的设备运行维护策略。 A single-phase grounding fault of a circuit breaker in its opening state occurred in a 500 kV GIS switch station in a large hydropower station,which led to the short line differential protection action on the joint incoming line of the units where the circuit breaker is located,and the disconnection of an operating unit.With the analysis of the protection fault recording,composition of the SF6 gas in the compartments in the fault range,and the fault circuit breaker,the cause of the fault is determined.By replacing the fault breaker,the problem is successfully solved.Also,some targeted operation and maintenance suggestions are proposed with an in-depth discussion of the fault.
作者 姜德政 任波 付鹏 熊舟 JIANG Dezheng;REN Bo;FU Peng;XIONG Zhou(Three Gorges Hydropower Plant, China Yangtze Power Co., Ltd., Yichang 443000, China)
出处 《水电与新能源》 2021年第1期41-43,47,共4页 Hydropower and New Energy
关键词 断路器 灭弧室 单相接地 电弧放电 短线差动保护 circuit breaker interrupter single-phase grounding arc discharge short line differential protection