摘要
本文利用热负荷延续时间图分析了用环境空气综合温度替代室外空气温度进行供热运行调节时的节能量。分析结果表明,在保证室内舒适度不变的前提下,以环境空气综合温度替代室外空气温度用于供热系统运行调节,可降低系统的供热量。在太阳资源三类地区,节能率为2.6%~4.4%;在太阳资源一类和二类地区,节能率为8.8%~11.5%。在太阳能资源越丰富的地区,节能率越大,节能潜力也越高。
In the paper,heating load duration graph was used to analyze the energy saving when the integrated temperature of ambient air could replace outdoor air temperature for heating operation regulation.The results showed that systematic heat load could be reduced when integrated temperature of ambient air was adopted in the operation of heat supply system instead of outdoor air temperature under a fixed indoor comfort degree.In the first and second tier region of solar energy resources,the energy conservation potential was between 8.8%and 11.5%;while in the third tier region,it was 2.6%to 4.4%.
作者
王磊
方修睦
乔正凡
杨萌
Wang Lei;Fang Xiumu;Qiao Zhengfan;Yang Meng(Central and Southern China Municipal Engineering Design and Research Institute Co.Ltd.;School of Architecture,Harbin Institute of Technology)
出处
《区域供热》
2021年第1期65-70,97,共7页
District Heating
关键词
环境
温度
热负荷
时间
节能率
environment
temperature
heat load
time
energy saving rate