期刊文献+

SPD与后备保护断路器配合性能研究 被引量:1

Study on the Coordination Performance of SPD and Backup Protective Circuit Breakers
下载PDF
导出
摘要 目前使用的后备保护断路器,由于不能与电涌保护器(SPD)协调配合,当电源异常或SPD劣化失效时,常导致火灾、设备遭雷击损坏事故的发生,针对这种情况,运用8/20μs、10/350μs波形模拟雷电流对多种型号后备保护器进行冲击试验测试和分断工频能力研究,对试验结果进行分析。结果表明,断路器不能限制瞬态过电压,且SPD短路失效时不能快速分断工频电流,应以SPD专用断路器取而代之。简要介绍了新型SPD专用断路器的原理,并对其性能进行了验证。 The current backup protection circuit breaker could not coordinate with the surge protection device(SPD).When the power supply was abnormal or the SPD was deteriorated,it often leaded to fire and equipment damage.In view of this situation,8/20μs and 10/350μs waveform were applied to simulate lighting current and complete impulse test and identify breaking power frequency ability of various types of backup protector.The results showed that the circuit breaker couldn’t limit the transient overvolage, and it couldn’t quickly break the power frequency current when SPD short circuit failed.Therefore,SPD special circuit breaker should be used instead.The principle of the new SPD special circuit breaker was briefly introduced,and its performance was verified.
作者 刘璇 王林峰 许延贺 刘宝全 毕晓蕾 高剑 姜辉 张长秀 刘娟 Liu Xuan;Wang Linfeng;Xu Yanhe;Liu Baoquan;Bi Xiaolei;Gao Jian;Jiang Hui;Zhang Changxiu;Liu Juan(State Key Laboratory of Safety and Control for Chemicals,SINOPEC Qingdao Research Institute of Safety Engineering,Shandong,Qingdao,266071;CNPC Changqing Oilfield Company,Shanxi,Xi′an 710016;SINOPEC Marketing Chongqing Company,Chongqing,400010)
出处 《安全、健康和环境》 2021年第2期34-38,共5页 Safety Health & Environment
基金 国家重点研发计划(2018YFF01010804),雷电静电监测与安全防护系统开发及应用 山东省重大科技创新工程项目(2019JZZY020501),原油储罐重大风险预警与防控技术研究及应用。
关键词 雷电防护 电涌保护器(SPD) 过电流保护 断路器 耐受电流 lightning protection SPD over-current protection circuit breaker withstand current
  • 相关文献

参考文献12

二级参考文献46

共引文献28

同被引文献8

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部