数据中心列间空调气流组织分析与优化 被引量:9

Analysis and optimization of airflow distribution in the data center
下载PDF
导出
摘要 以小型数据服务机房为研究对象,对机房使用列间空调后的气流组织进行了分析。利用CFD(流体动力学)软件对房间内的气体流动情况进行模拟,绘制温度、矢量风速计算云图,对比了冷通道封闭前后房间温度场、风场的变化,分析封闭前后室内换热情况。研究发现,冷通道封闭后离地0.5、1.5 m处平均温度较封闭前平均温度下降2℃左右,机柜顶面下降1℃左右。封闭冷通道能够优化气流组织,有效避免气流短路,机房内局部热点消失,无效换热减少。 With the small data service room as the research object,the airflow distribution of the room after using in-row air conditioning was analyzed.By using CFD(hydrodynamics)software,the airflow in the roomwas simulated,the temperature and vector wind speed calculation clouds were drawn.The temperature field and flow field before and after the cold channel closure were compared,and the indoor heat transfer was analyzed.Results show that after closing the cold channel the average temperature at 0.5 m and 1.5 m above the ground is about 2℃lower than before,and the top of the cabinet is about 1℃lower.Closing the channel can optimize the airflow distribution and avoid the short circuit of airflow effectively.Meanwhile,the local hot spots disappear,and invalid heat transfer is reduced.
作者 邱玉英 邱琳祯 QIU Yuying;QIU Linzhen(Fujian Chuanzheng Communications College, Fuzhou 350007, China;Fujian Academy of Architectural Sciences Co., Ltd, Fuzhou 350108, China;Fujian Key Lab of Green Building Technology, Fuzhou 350108, China)
出处 《福建工程学院学报》 CAS 2021年第1期84-88,共5页 Journal of Fujian University of Technology
关键词 列间空调 气流组织 冷通道 数据机房 in-row air conditioning air distribution cold channel data room
  • 相关文献

参考文献10

二级参考文献51

  • 1林章,周天泰,曾志宽.层式通风——高温空调下的出路[J].化工学报,2008,59(S2):235-241. 被引量:19
  • 2么淑倩,韩建芳,王衡.大空间建筑模型上送风空调数值模拟[J].山西建筑,2005,31(13):152-153. 被引量:3
  • 3韩有文,彭涛,陈创新.机房空调利用风道实现节能降耗[J].电信技术,2007(2):79-80. 被引量:6
  • 4中国电子工程设计院.GB50174-2008电子信息系统机房设计规范[S].北京:中国计划出版社,2009.
  • 5云计算发展与政策论坛.数据中心能效测评指南[C].2012.
  • 6Environmental Protection Agency. Report to congress on server and data center energy efficiency [-R. Public Law 109-431. U S, 2007.
  • 7Sun H S, Lee S E. Case study of data centers' energy performance[J. Energy and Buildings, 2006,38 (5) . 522-533.
  • 8Koomy J G. Growth in data center electricity use 2005 to 2010 EEB/OL. E2011 http: /// www. analyticspress, eom/datacenters, html.
  • 9ASHRAE. ASHRAE TC 9.9 Thermal guidelines for data processing environments expanded data center classes and usage guidanceES, 2011.
  • 10Sharma R K, Bash C E, Patel R D. I)imensionless parameters for evaluation of thermal design and performance of large-scale data centersC// In 8th ASME/AIAA Joint Thermophysies and Heat Transfer Conference, 2002.

共引文献111

同被引文献46

引证文献9

二级引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部