期刊文献+

一起110kV变电站事故总异常告警的故障分析 被引量:3

Fault Analysis of Abnormal Alarm for Integrated Accident Signals in 110 kV Substation
下载PDF
导出
摘要 针对一起110 kV变电站巡视中发现的间隔事故总异常告警事件,通过原理分析、回路检查,逐步排查出变更防跳回路导致的合闸监视回路失配是造成事故总异常告警的主要原因,在此基础上给出缺陷整改措施并成功消缺,最后给出防范及改进措施,避免此类事件的再次发生。 To a alarm event of interval integrated accident signals found in the inspection of a 110 kV substation,through the principle analysis and circuit inspection,it was found out that the main cause was the mismatch of closing monitoring circuit caused by alteration of the anti-tripping circuit.On this basis,the defect rectification measures were given and the defects were eliminated successfully.Finally,preventive and improvement measures were given to avoid the recurrence of such incidents.
作者 孔凡坊 胡红霖 刘尚孟 KONG Fanfang;HU Honglin;LIU Shangmeng(Wenzhou Power Supply Company of State Grid Zhejiang Electric Power Co.,Ltd.,Wenzhou 325000,China)
出处 《电工技术》 2021年第3期109-111,共3页 Electric Engineering
关键词 变电站 事故总信号 合闸监视 防跳 substation integrated accident signals closing monitoring anti-trip
  • 相关文献

参考文献4

二级参考文献9

共引文献7

同被引文献38

引证文献3

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部