摘要
目前孤岛检测研究中鲜有针对不同控制策略并存时被动法检测性能的研究分析,选取过欠电压检测法与过欠频率检测法,面向电流控制策略与功率控制策略并存场景,通过求取其检测盲区解析解并分析可得,负荷品质因数和负荷消耗无功与有功的比值只影响过欠频率检测法检测盲区,不同控制型逆变器输出有功与负荷消耗有功的比值主要影响过欠电压检测法检测盲区,同时并存场景下与单一控制策略下的检测盲区存在显著差别。
In view of the problems that the detection performance analysis of passive methods are rarely studied in islanding detection research when different control strategies coexist,facing the co-existence of current control strategy and power control strategy,the non-detection zone of the over/under voltage detection method and the over/under frequency detection method are analyzed.The non-detection zone expression is obtained by solving analytical solution and the conclusions are depicted as follows:the load quality factor and the ratio of reactive power to active power consumed by load only affect the non-detection zone of over/under frequency detection method,and the ratio of active power generated by inverters to active power consumed by load under different control strategies mainly affect the non-detection zone of over/under voltage detection method.Simultaneously,there are significant differences between the non-detection zone in the different control strategies coexisting scenario and the single control strategy scenario.
作者
王阳光
张孝军
徐宇新
黄勇
吴宇奇
叶雨晴
马啸
王子璇
李正天
WANG Yangguang;ZHANG Xiaojun;XU Yuxin;HUANG Yong;WU Yuqi;YE Yuqing;MA Xiao;WANG Zixuan;LI Zhengtian(State Grid Hunan Electric Power Co.,Ltd.,Changsha 410004,China;State Key Laboratory of Advanced Electromagnetic Engineering and Technology,Huazhong University of Science and Technology,Wuhan 430074,China)
出处
《电力自动化设备》
EI
CSCD
北大核心
2021年第4期109-115,共7页
Electric Power Automation Equipment
基金
国家自然科学基金面上资助项目(51877088)
国网湖南省电力有限公司科技项目(5216A018007W)。
关键词
微电网
电流控制策略
功率控制策略
过欠电压
过欠频率
检测盲区
microgrid
current control strategy
power control strategy
over/under voltage
over/under frequency
non-detection zone