摘要
针对GW7B-550型接地开关3个固定螺栓掉落,1个松脱情况,理论仿真计算和模拟试验分析接地开关受力情况,最终确定由接地刀闸导电杆与传动曲臂连接异常、闭锁失效,在大风外力作用下,导电杆逐步抬起,造成单相接地引发故障。
In view of the drop of 3 fixing bolts and one loosening of the GW7B-550 grounding switch,the stress of grounding switch is analyzed by theoretical simulation calculation and simulation test.Finally,it is determined that the connection between the conductive rod of the grounding knife switch and the transmission crank arm is abnormal and the locking is invalid.Under the action of strong wind,the conducting rod is gradually raised,resulting in single-phase ground fault.
作者
田世济
房崇峰
高田雨
TIAN Shiji;FANG Chongfeng;GAO Tianyu(Jilin Jidian Power Distribution Co.,Ltd.,Changchun 130012,China;Siping Power Supply Company,State Grid Jilin Electric Power Co.,Ltd.,Siping 136000,China;Changchun Power Supply Company,State Grid Jilin Electric Power Co.,Ltd.,Changchun 130000,China)
出处
《电工技术》
2021年第4期83-84,共2页
Electric Engineering
关键词
接地刀闸
理论仿真
模拟试验
单相接地
grounding knife gate
theoretical simulation
simulation test
single-phase grounding