期刊文献+

具有烟囱效应的某铁路隧道紧急出口防烟系统设计 被引量:1

Design of Smoke Control System for the Emergency Exit of Railway Tunnels with Chimney Effect
下载PDF
导出
摘要 为解决某铁路隧道长大上坡式紧急出口在冬季防护门断面处无法产生防烟正压风速的问题,对该隧道长度、坡度、内部温度、环境温度等进行分析,认为该紧急出口存在较为严重的烟囱效应。建立计算机仿真模型,分别采用增加防烟射流风机、增设挡风墙和改建避难所3种解决方案,模拟在夏季、冬季、火灾工况的防烟效果,并对结果进行分析。证实了改建为封闭式避难所的方案可以确保紧急出口防护门断面处产生稳定的正压风速,并对避难所疏散门设置、硬件补强措施和疏散注意要点等提出建议。 In order to solve the problem that railway tunnels with long uphill emergency exit cannot produce positive pressure ventilation to stop the spread of smoke in the section of emergency exit in winter,the author analyzed the tunnel length,slope,internal temperature and environmental temperature,and concluded that there is a serious chimney effect at the emergency exit.To solve this problem,the author establishes a computer simulation model,and adopts three solutions:adding jet fan,adding wind break wall and rebuilding a fully enclosed shelter.It is proved that the scheme of rebuilding a closed shelter can ensure the stable positive pressure ventilation at the emergency exit.At last,some suggestions are put forward,including installing an evacuation door,hardware reinforcement and evacuation tips.
作者 秦宁然 戴忠 樊刘昌 于翔 QIN Ningran;DAI Zhong;FAN Liuchang;YU Xiang(Chengdu Railway Public Security Bureau,Sichuan Province 610081,China;Railway Public Security Bureau of Ministry of Public Security,Beijing 100844,China;National Center for Fire Engineering Technology,Tianjin 300382,China)
出处 《武警学院学报》 2021年第4期10-14,共5页 Journal of the Armed Police Academy
关键词 铁路隧道 紧急出口 防烟系统 烟囱效应 斜井 避难所 railway tunnel emergency exit smoke control system chimney effect inclined shaft shelter
  • 相关文献

参考文献7

二级参考文献34

  • 1安玉红.铁路隧道防灾救援疏散工程设计研究[J].石家庄铁道大学学报(自然科学版),2013,26(S2):99-104. 被引量:16
  • 2涂文轩.我国铁路隧道列车火灾简介[J].消防技术与产品信息,1996,9(1):26-27. 被引量:11
  • 3杜守良.辽源市中心医院火灾原因调查案例分析[J].消防科学与技术,2007,26(1):98-100. 被引量:11
  • 4J S Petraglia. fire risk for blind or visually impairment[ EB/OL]. [2012-10-10]. http: //www. google, com.
  • 5姜传胜.残疾人疏散安全研究现状与发展趋势[J].中国安全科学报,2009(19):161-166.
  • 6美国的《生命安全规范》2012版(NFPAl01)[EB/OL].[2012-10-10].http://www.google.corn.
  • 7A Sekizawa, S Nakahama, M Ebihara, H. et al, Study on Feasi- bility of Evacuation by Elevators in a High-rise Building-Case Study for the Evacuation in the Hiroshima Motomachi High-rise A- partments[ C ]//Proceedings of the Second International Symposi- um on Human Behaviour in Fire. Boston, USA, 2001 : 65 -76.
  • 8郭春,王明年,赵海东.铁路特长隧道火灾应急救援问题研究[J].中国安全科学学报,2007,17(9):153-158. 被引量:24
  • 9Diamantidis D, Zuccarelli F, Westhauser A. Safety of long railway tunnels [ J ]. Reliability Engineering and System Safety, 2000(67) : 135 - 145.
  • 10Anders Lonnermark. On the characteristics of fires in tunnels [ D ]. Sweden : Lund University, 2005.

共引文献65

同被引文献19

引证文献1

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部