摘要
介绍了某35 kV变电站一台35 kV主变有载调压开关在切换过程中发生桥接电阻断裂,引起内部弧光放电,造成油质劣化的事故。分析原因为变压器高压侧无保护运行,有载调压开关长时间故障引起主变本体相间短路,导致主变高压侧对侧线路后备保护动作跳闸,主变停运。最后针对此次事故,提出了相应的防范措施。
When a 35 kV main transformer load voltage regulator was switching in a 35kV substation,the bridge resistance broke,causing internal arc discharge and oil deterioration.The reason was analyzed.Because the transformer is unprotected,the long-time fault of the on load tap changer causes the phase to phase short circuit fault of the main transformer body,which leads to the tripping of the line backup protection at the high voltage side of the main transformer and the main transformer outage.Finally,corresponding preventive measures are proposed for this accident.
作者
吕强
王青霞
侯少帅
赵全胜
石云松
李晓飞
刘霖
王文利
郭峰
李军
LV Qiang;WANG Qingxia;HOU Shaoshuai;ZHAO Quansheng;SHI Yunsong;LI Xiaofei;LIU Lin;WANG Wenli;GUO Feng;LI Jun(Zhengzhou Power Supply Company,State Grid Henan Electric Power Company,Zhengzhou 450006,China)
出处
《电工技术》
2021年第5期83-85,共3页
Electric Engineering
关键词
有载调压开关
桥接电阻
相间短路故障
过流保护
load voltage regulator
bridge resistance
interphase short circuit failure
overcurrent protection