机房空调对数据中心热环境影响的模拟研究 被引量:2

Simulation Study of the Effect of Air Conditioning on Data Center Thermal Environment
下载PDF
导出
摘要 以重庆某数据中心为例,实测发现机房空调在回风控制下存在实际运行参数不一致,回风温度设定值不合理的问题,导致机房热环境不均匀,空调能耗浪费。利用6SigmaRoom软件模拟空调采取群控策略和不同回风温度下的机房热环境,结果表明,空调群控可以提高热环境均匀性,最高环境温度下降3.5℃,SHI值从0.036下降到0.005。空调推荐设定回风温度为27℃,适当提高回风温度可以在不引起过热的情况下节约39.5%的空调风机能耗。 In this paper, a data center in Chongqing is taken as an example. Through actual measurement, it is found that under the return air control mode, the computer room air conditioner has inconsistent actual operating parameters, and the return air temperature setting value is unreasonable. As a result, the thermal environment of the server room is uneven, and air conditioning energy is wasted. The 6 SigmaRoom software is used to simulate the thermal environment with air conditioning group control strategy and at different return air temperatures. The results show that group control can improve the uniformity of the thermal environment. Maximum ambient temperature drops by 3.5 ℃,and SHI drops from 0.036 to 0.005. The return air temperature is recommended to set to 27 ℃, which can save 39.5% of the air conditioning fan energy consumption without causing overheating.
作者 傅珏忻 白雪莲 金超强 FU Jue-xin;BAI Xue-lian;JIN Chao-qiang(School of Civil Engineering,Chongqing University)
出处 《建筑热能通风空调》 2021年第3期85-88,28,共5页 Building Energy & Environment
基金 国家自然科学基金(No.51778080)。
关键词 数据中心 机房空调 群控 回风温度 热环境 data center computer room air conditioner group control return air temperature thermal environment