摘要
介绍一起发变组过励磁反时限保护误动引起机组跳闸故障,通过对现场DCS系统指令及参数图、现场动作报告、保护装置校验等进行分析,确定发变组过励磁反时限保护基准值偏差引起保护误动,是导致机组跳闸的直接原因,并提出了针对性的处理及防范措施,避免类似故障发生。
This paper introduces an accident of generator-transformer over-excitation inverse time protection misoperation, through analysis on the DCS system instructions and parameter, action reports, protection device verification, identifies the cause of this misoperation are that the reference value deviation of the generator-transformer over-excitation inverse time protection causes the protection to malfunction, which is the direct cause of the unit trip. At last, proposes the preventive measures after the analysis to avoid similar faults.
作者
胡伟
HU Wei(Handan Cogeneration Power Plant,Handan 056004,China)
出处
《河北电力技术》
2021年第2期60-62,共3页
Hebei Electric Power
关键词
发变组保护
过励磁保护
基准值偏差
误动分析
generator-transformer protection
over-excitation protection
reference value deviation
misoperation analysis