期刊文献+

电炉变压器直流电阻异常分析及对策 被引量:1

Analysis on Anomaly in Direction Current Resistance of Electric Furnace Transformer and Countermeasures
下载PDF
导出
摘要 针对攀钢集团攀枝花钢钒有限公司炼钢厂电炉变压器大修后调压绕组线圈直流电阻存在的异常现象,分析后确定是有载分接开关缺陷导致。通过对有载分接开关进行吊芯处理,线圈直流电阻恢复正常,保证了变压器的大修质量。 With regard to the abnormal phenomena occurred in direction current resistance of the voltage regulating winding coil after the complete overhaul for the electric furnace transformer was done in Steelmaking Plant of Panzhihua Steel and Vanadium Co.,Ltd.of Pangang Group,it was concluded after analysis that the cause leading to the abnormal phenomenon was due to the on-load tap switch defect.After handling the on-load tap switch by lifting the core,the direction current resistance of the coil was back to normal,which guaranteed the overhaul quality of the transformer.
作者 杨龙 杨新胜 Yang Long;Yang Xinsheng(Construction Branch of Engineering Technology Co.,Ltd.of Pangang Group,Panzhihua 617000,Sichuan,China)
出处 《鞍钢技术》 CAS 2021年第3期61-65,共5页 Angang Technology
关键词 电炉变压器 直流电阻 有载分接开关 electric furnace transformer direction current resistance on-load tap switch