一起海陆缆混合线路接地电流异常原因分析 被引量:3

Abnormal Grounding Current Analysis of Land and Submarine Cable Hybird Line
原文传递
导出
摘要 接地电流是判断高压电缆接地方式是否正确的重要指标之一。笔者介绍了一起220 kV海陆缆混合线路接地电流异常事件,分析了该线路陆缆段中间接头和海陆缆对接头多处接地电流存在严重的三相不平衡现象产生的原因,并给出了接地方式优化方案。线路消缺后接地电流恢复正常,验证了所提出的处理措施的正确性。该起接地电流缺陷及其处理方案为采用海陆缆对接方式线路的接地方式选择提供了经验。 The grounding current is one of the important indexes to judge whether the grounding mode of HV cable is correct or not. The author introduces a grounding current defect of 220 kV land and submarine cable hybird line. The grounding currents of the middle joints of the land cable and the joints between the land and submarine cable of this line were seriously unbalanced. The reasons of unbalanced grounding currents were analyzed. Then,the optimization scheme of grounding mode was proposed. After eliminating the defeats,the grounding current returns to normal,and the correctness of the proposed treatment measures is verified. This grounding current defect and its treatment provides valuable experience for the grounding mode selection of land and submarine cable hybird lines.
作者 李乃一 曹俊平 王少华 邵先军 任广振 郭锋 俞恩科 LI Naiyi;CAO Junping;WANG Shaohua;SHAO Xianjun;REN Guangzhen;GUO Feng;YU Enke(State Grid Zhejiang Electric Power Co.,Ltd.,Research Institute,Hangzhou 310014,China;State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310007,China;State Grid Zhejiang Electric Power Co.,Ltd.,Zhoushan Power Supply Company,Zhoushan 316021,China)
出处 《电瓷避雷器》 CAS 北大核心 2021年第2期206-211,共6页 Insulators and Surge Arresters
基金 国网浙江省电力有限公司科技项目(编号:5211DS19002Z)。
关键词 海陆缆混合线路 接地方式 接地电流 多点接地 回流缆 缺陷分析 land and submarine cable hybird lines grounding mode grounding current multi-point grounding return cable defect analysis
  • 相关文献

参考文献8

二级参考文献109

共引文献147

同被引文献58

引证文献3

二级引证文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部