回热器位置对复叠式压缩制冷系统性能的影响 被引量:5

Effect of the regenerator position on the performance of compression cascade refrigeration system
原文传递
导出
摘要 为提高复叠式压缩制冷系统的低温制冷性能,采用R1234yf为工质,对三种回热器设置方式的复叠式压缩制冷系统进行能量分析和[火用]分析。结果表明,三种回热器设置方式都可以提高系统性能,其中高低温级同时设置回热器对系统性能提高最多,COP可提高12.21%,[火用]效率可提高11.68%;其次为仅设置高温级回热器时,COP提高10.69%,[火用]效率提高10.57%;仅设置低温级回热器时,系统COP和[火用]效率提高最少,分别提高2.29%,1.98%。 In order to improve the low-temperature refrigeration performance of the cascade compression refrigeration system, R1234 yf was used as the working refrigerant, energy and exergy analyses were performed on the cascade compression refrigeration system with three regenerator settings. The results show that all three types of regenerator settings can improve system performance. Among them, setting the regenerator at the same time for the high and low temperatures can improve the system performance the most, COP can be increased by 12.21%, and the exergy efficiency can be increased by 11.68%. The second is that when only the high temperature regenerators are installed, COP is increased by 10.69% and the exergy efficiency is increased by 10.57 %;When only low-temperature-grade regenerators are installed, the system COP and exergy efficiency increase the least, increasing by 2.29% and 1.98%, respectively.
作者 张普洋 李风雷 Zhang Puyang;Li Fenglei(College of Civil Engineering,Taiyuan University of Technology,Taiyuan 030024,China)
出处 《低温与超导》 CAS 北大核心 2021年第5期71-76,共6页 Cryogenics and Superconductivity
基金 山西省重点研发计划(201803D31036) 山西省科技攻关项目(2016-032)资助。
关键词 回热器 复叠制冷 能量分析 [火用]分析 Regenerator Cascade refrigeration Energy analysis Exergy
  • 相关文献

参考文献2

二级参考文献19

  • 1张术学.CO_2/NH_3复叠制冷浅析[J].制冷与空调,2006,6(1):59-62. 被引量:9
  • 2陈光明,陈国邦.制冷与低温原理[M].北京:机械工业出版社,2002.
  • 3Kitzmiller W R. Advantages of CO2-Ammoniasystem for low-temperature refrigeration [J]. Power, 1932 (1) :92-94.
  • 4Pettersen A J ,Jakobsen A. A dry ice slurry system for low temperature refrigeration [C] // International Symposium on Refrigeration in Sea Transport Today and in the Future. Gdansk, Poland, 1994 : 1 -18.
  • 5胡姆·格贝哈尔特.Nestle公司采用NH,和CO2制冷剂-采用天然制冷剂替代R1381的一个大型冷库[J].制冷与空调技术,2002(1):46-52.
  • 6Kuniaki Kawamura, S Akaboshi, Akito Machida. De- sign Considerations for an NH3 System Utilizing CO2 as a secondary Refrigerant in Kokyo[C]//2008 Ⅱ AR Ammonia Refrigeraion Conference & Exhibition. 2008.
  • 7金嘉玮,叶尉南,杨一凡.CO_2/NH_3复叠式制冷系统在美国大型冷库的应用实例[J].冷藏技术,2007,30(2):1-9. 被引量:16
  • 8KLEIN S A, REINDL D T, BROWNELL K. Refrigeration system performance using liquid-suction heat exchangers[J]. International JournalofRefrigeration, 2000, 23 (8): 588-596.
  • 9MESS1NEO A. R744-R717 cascade refrigeration system : performance evaluation compared with a HFC two-stage system[J]. EnergyProcedia, 2012 (14): 56-65.
  • 10TORRELLA E, SANCHEZ D, LLOPIS R, et al. Energetic evaluation of an internal heat exchanger in a CO2 transcritical refrigeration plant using experimental data[J]. International Journal of Refrigeration, 2011, 34 (1): 40-49.

共引文献15

同被引文献52

引证文献5

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部