±350 kV鲁西背靠背柔性直流阀控系统设计缺陷及改进措施 被引量:6

Design Defects and Improvement Suggestions of ±350 kV Luxi Back-to-back Flexible DC Valve Control System
下载PDF
导出
摘要 针对鲁西背靠背柔性直流输电工程两起阀控系统单一通信元件故障导致的柔性直流闭锁事件进行了原因分析。认为因阀控系统并非完全冗余设计,控制两套阀控系统切换的通信EX板为共用设备,存在EX板故障后依然上传阀控系统错误跳闸信息,阀控系统执行故障判断逻辑并出口闭锁柔性直流系统的情况。为此提出执行通信EX板故障校验机制,将两套系统切换通信EX板改造为双套冗余配置等改进措施,避免单一通信元件故障导致柔性直流闭锁事件的发生。 This paper analyzes the causes of two flexible DC blocking events caused by single communication component failure of valve control system in Luxi back-to-back flexible DC project.It is considered that because the valve control system is not a completely redundant design,the communication EX board controlling the switching between the two valve control systems is a common device,and there is a situation that after the EX board fails,it will still upload the wrong trip information of the valve control system,and the valve control system executes the fault judgment logic and locks the flexible DC at the outlet.In order to avoid the occurrence of flexible DC blocking event caused by single communication component failure,the improvement measures such as implementing communication EX board fault checking mechanism are proposed,which transforms two sets of system switching communication EX board into two sets of redundant configuration.
作者 褚海洋 冉学彬 莫跃 宋海彬 毛臻炫 关宇洋 包也 CHU Haiyang;RAN Xuebin;MO Yue;SONG Haibin;MAO Zhenxuan;GUAN Yuyang;BAO Ye(Tianshengqiao Bureau,China Southern Power Grid Ultra High Voltage Transmission Company,Xingyi 562400,China)
出处 《内蒙古电力技术》 2021年第3期66-70,共5页 Inner Mongolia Electric Power
基金 南方电网超高压输电公司科技项目“鲁西站柔直功率模块故障诊断技术研究”(CGYKJXM20180354)。
关键词 柔性直流输电 阀控系统 通信元件 闭锁 双套冗余 flexible DC transmission valve control system communication element locking double set of redundancy
  • 相关文献

参考文献14

二级参考文献161

共引文献216

同被引文献134

引证文献6

二级引证文献8

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部