期刊文献+

Dynamic State Estimation Based Protection of Mutually Coupled Transmission Lines

原文传递
导出
摘要 Mutually coupled lines create challenges for legacy protection schemes.In this paper,a dynamic state estimation based protection(EBP)method is proposed to address these challenges.The method requires GPS synchronized measurements at both ends of the line and a high fidelity model of the protected line.The paper presents the dynamic model of the protected line and its impact on the performance of the protection scheme.Numerical simulations prove that the method can correctly identify faults,independent of position and type.The work also demonstrates the advantages of the proposed method versus legacy protection functions such as distance protection and line differential.These advantages include reliable and faster detection of internal low impedance faults,inter-circuit faults,and high impedance faults,even in cases of 1)partially coupled lines and 2)lack of measurements in adjacent lines.
出处 《CSEE Journal of Power and Energy Systems》 SCIE 2016年第4期6-14,共9页 中国电机工程学会电力与能源系统学报(英文)
基金 supported by the Electric Power Research Institute(EPRI)and the Power Systems Engineering Research Center(PSERC).