摘要
利用Raman光谱技术对火灾中铜导线火烧熔痕的附着碳进行检测,分析了样品光谱的峰位、峰形及峰强等光谱特征,同时使用五带拟合法对Raman光谱进行分峰拟合后,进行定量分析。结果表明:不同火场温度以及作用时间的铜导线火烧样品的Raman光谱差异性较大,火烧熔痕样品Raman光谱的D1峰半峰宽小、峰强大,ID2/IG趋近于0,ID3/IG、ID4/IG较小。研究结论说明Raman光谱法可有效鉴识火烧熔痕,为研究火灾原因提供指导意见。
In this paper,Raman spectral is used to test the adherent carbon of the copper conductor burned globules.The spectral characteristics such as peak position,peak shape and peak intensity of the sample spectrum are analyzed.And quantitative analysis of the Raman spectra is also performed after the peakdifferentiating using the five-band differentiating method.The results show that the Raman spectra of the burned globules wire samples with different fire temperatures and time are quite different.The width of the half D1 peak is small and the peak intensity is strong.ID2/IG approaches 0,ID3/IG and ID4/IG is relatively small.The conclusion of the study indicates that the Raman spectrum can effectively identify the burning traces of the globules,and provide guidance for the research of the cause of fire.
作者
丁诗懿
杨涵
汪箭
DING Shi-yi;YANG Han;WANG Jian(Hangzhou Fire and Rescue Division,Zhejiang Hangzhou 310000,China;State Key Laboratory of Fire Science,University of Science and Technology of China,Anhui Hefei 230026,China)
出处
《消防科学与技术》
CAS
北大核心
2021年第6期929-932,共4页
Fire Science and Technology
基金
国家自然科学基金项目(51991352)。
关键词
熔痕
火烧
RAMAN光谱
定量分析
火灾原因
globules
burning traces
Raman spectrum
quantitative analysis
cause of fire