摘要 Air velocity and temperature distributions inside operating rooms (ORs) play a crucial role to reduce the risk of infections and to ensure adequate comfort conditions for patient and medical staff. In this work, the authors have developed a three-dimensional thermo-fluid dynamic model to simulate airflow and thermal comfort in an actual OR equipped with High-Efficiency Particulate Air (HEPA) filters. The model takes into account the presence of surgical lights, people and equipment within the room. An experimental campaign is carried out inside the actual OR to measure velocity and temperature, to be employed as boundary conditions for the numerical model. The experimental data have also been used to validate the numerical results. The validated model has been used to analyze the effects of human shape, thermal boundary conditions and buoyancy forces on the main thermal and fluid dynamic quantities in the OR. The thermal comfort is evaluated based on Predicted Mean Vote (PMV) and Predicted Percentage of Dissatisfied (PPD) indices. The results prove that the present experimental-numerical approach is useful to analyze and improve the thermal comfort conditions for medical staff and patient.
出处 《Building Simulation》 SCIE EI CSCD 2021年第4期1127-1146,共20页 建筑模拟(英文)
  • 相关文献

参考文献3

二级参考文献45

  • 1ANSI/ASHRAE 55-1992. (1992). ASHRAE standard: Thermal environmental conditions for human occupancy. ASHRAE Standing Standard Project Committee 55.
  • 2Buchanan, C. R., & Dunn-Rankin, D. (1998). Transport of surgically produced aerosols in an operating room. American Industrial Hygiene Association Journal, 59, 393-402.
  • 3Burman, L. G. (2006). Art forebygga vardrelaterade infektioner - Ett kunskap- sunderlag. Stockholm: Swedish National Board of Health and Welfare., ISBN 9185482145.
  • 4Chen, F., Yu, S. C. M., & Lai, A. C. K. (2006). Modeling particle distribution and deposition in indoor environments with a new drift-flux model Atmospheric Environment, 40(2), 357-367.
  • 5Chow, T.-T., & Wang, J. (2012). Dynamic simulation on impact of surgeon bend- ing movement on bacteria-carrying particles distribution in operating theatre. Building and Environment, 57, 68-80.
  • 6Chow, T.-T., & Yang, X.-Y. (2003). Performance of ventilation system in a non-standard operating room. Building and Environment, 38(12), 1401-1411.
  • 7Chow, T.-T., & Yang, X.-Y. (2005). Ventilation performance in the operating theatre against airborne infection: Numerical study on an ultra-clean system.Journal of Hospital Infection, 59(2), 138-147.
  • 8Davies, R. R., & Noble, W. C. (1962). Dis persal of bacteria on desq uamated skin. Lancet, 2(7269), 1295-1297.
  • 9de Dear, R., Arens, E., Zhang, H., & Oguro, M. (1997). Convective and radiative heat transfer coefficients for individual human body segments. International Journal of Biometeorology, 40(3), 141 - 156.
  • 10Friberg, S., Ardnor, B., Lundholm, R., & Friberg, B. (2003). The addition of a mobile ultra-clean exponential laminar airflow screen to conventional operating room ventilation reduces bacterial contamination to operating box levels. Journal of Hospital Infection, 55(2), 92-97.