期刊文献+

一起220kV变压器局部放电故障的诊断及分析 被引量:14

Fault Diagnosis and Analysis of Partial Discharge in 220kV Transformer
下载PDF
导出
摘要 介绍了一起220kV电力变压器局部放电检测及诊断案例。根据运行期间油色谱检测数据,判定变压器内部存在低能放电缺陷。采用多种带电检测技术进行综合诊断,分析变压器内部存在悬浮放电缺陷的原因。通过对缺陷处理后的变压器进行跟踪复测,验证了带电检测技术的准确性和有效性。 A field application case of 220 kV power transformer partial discharge detection and diagnosis is introduced.According to the data of oil chromatography during operation,the defect of low energy discharge in transformer is determined.The causes of suspension discharge existing in the transformer are analysed by using a variety of live detection techniques to cpmprenensive diagnosis.The accuracy and effectiveness of the live detection technology are verified by tracking and retest of the transformer after defect treatment.
作者 包玉树 黄亚龙 许蔺 孙雄 胡永建 李炯 BAO Yu-shu;HUANG Ya-long;XU Lin;SUN Xiong;HU Yong-jian;LI Jiong(Jiangsu Frontier Electric Technology Co.,Ltd.,Nanjing 211102,China;Shanghai Sichuang Electrical Equipment Co.,Ltd.,Shanghai 201322,China)
出处 《变压器》 2021年第7期75-78,82,共5页 Transformer
关键词 变压器 局部放电 油色谱 带电检测 故障诊断 Transformer Partial discharge Oil chromatography Live detection Fault diagnosis
  • 相关文献

参考文献5

二级参考文献35

共引文献56

同被引文献155

引证文献14

二级引证文献29

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部