摘要 为了解决一起液压机构频繁打压问题,笔者通过对该液压机构和储能控制回路进行检查分析,发现液压机构存在渗漏,且由于受到环境温度变化的影响而导致液压机构夜间频繁打压。通过更换渗漏部件和优化储能控制回路等方法解决了该断路器的频繁打压问题,并对该类型断路器的液压机构检修维护提出了针对性的建议,为今后解决类似的问题起到一定的借鉴作用。 In order to solve the problem of frequent bulge of hydraulic mechanism,the authors check and analyze the hydraulic mechanism and energy storage control circuit,and find that the leakage of the hydraulic mechanism and the frequent bulge of the hydraulic mechanism at night due to the influence of environmental temperature change.The frequent bulge of the circuit breaker is solved by replacing the leakage components and optimizing the energy storage control circuit.The maintenance of the hydraulic mechanism of the circuit breaker is put forward,which plays a certain reference role in solving similar problems in the future.
作者 祖武强 霍克伟 ZU Wuqiang;HUO Kewei(State Grid Henan Electric Power Corporation Maintenance Company,Zhengzhou,Henan,450007;State Grid Henan Electric Power Corporation Puyang Power Supply Company,Puyang,Henan,457000)
出处 《红水河》 2021年第4期113-116,共4页 Hongshui River
关键词 断路器 频繁打压 液压机构 circuit breaker frequent bulge hydraulic mechanism
  • 相关文献

参考文献4

二级参考文献7

  • 1电力行业技能鉴定指导中心编.变电检修.中国电力出版社,2006年.
  • 2GB1984-2003高压交流断路器.中华人民共和国国家质量监督检验检疫局.2003-06-05发布.
  • 3和中浩.液压系统设计和维修基础[M].重庆:重庆西南师范大学出版社,1995.
  • 4刘文浩.LW6系列SF6断路器检修工艺[M].武汉:华中电管局,1993.
  • 5稽光国,吕淑华,等.液压系统故障诊断与排除[M].北京:海洋出版社,1992.
  • 6韦斌.SF_6断路器异常打压原因分析及解决方法[J].南方电网技术,2008,2(6):96-98. 被引量:8
  • 7郑俊洋,司雪峰,段利伟.LW10B-252型断路器机构打压频繁的分析[J].高压电器,2009,45(2):120-121. 被引量:15