期刊文献+

resonance±11.2kV直流融冰装置换流变低压侧电压互感器中性点接地问题探讨

Discussion on Neutral Grounding of Converter Transformer on Low Voltage Side of±11.2 kV DC Deicer
下载PDF
导出
摘要 直流融冰装置在进行融冰时,可能出现换流变低压侧电压互感器熔丝熔断、电压互感器爆炸的问题。分析了该事故产生的机理及抑制措施,并提出了一种解决融冰过程中谐振问题的办法。 When the DC ice melting device is melting ice,the fuse of the voltage transformer on the low-voltage side of the converter transformer may be blown and the voltage transformer may explode.The mechanism and restraining measures of the accident are analyzed,and the physical simulation results are given.A solution is proposed to solve the resonance problem in the ice melting process:the primary side coil of the low-voltage side voltage transformer of the converter transformer is changed to a neutral point non-grounding method.
作者 李斌 Li Bin
出处 《电力系统装备》 2021年第12期15-17,共3页 Electric Power System Equipment
关键词 直流融冰装置 电压互感器 中性点 谐振 DC ice melting device voltage transformer neutral point resonance
  • 相关文献

参考文献2

二级参考文献3

  • 1[1]北京网联直流咨询公司.西北-华中联网背靠背直流工程功能规范书[Z].北京:北京网联直流输电系统工程有限公司,2001,11.
  • 2[2]马为民.成套设计《主回路参数设计》技术报告[Z].北京:北京网联直流输电系统工程有限公司,2002.
  • 3[4]武汉高压研究所.三峡直流输电工程咨询研究项目,同廊道架设的交直流线路之间的相互影响研究[R].武汉:武汉高压研究所,1997.