期刊文献+

Enhancing HVRT Capability of DFIG-based Wind Farms Using Cooperative Rotor-side SMES Considering the Blocking Fault of LCC-HVDC System 被引量:6

原文传递
导出
摘要 Line-commutated converter based high voltage direct current(LCC-HVDC)has been applied for transferring bulk power from wind farms to load centers through long distances in many countries.When the blocking fault of the LCC-HVDC system occurs,the surplus reactive power accumulated at the sending end will lead to an overvoltage,thus causing the discon・nection of the wind turbines.To maintain the reliable connection of wind turbines and ensure the stability of the power system,this paper introduces a superconducting magnetic energy storage(SMES)unit to connect in parallel with the rotor side of the doubly fed induction generator(DFIG).By controlling the energy side converter and rotor side converter to inject demagnetizing current and reactive current into the rotor,the proposed scheme can effectively stabilize key parameters of the wind turbine and provide desirable reactive power support,showing a favorable high voltage ride through(HVRT)performance.Several cases based on PSCAD/EMTDC&MATLAB/Simuiink co-simulation together with economic analysis are conducted to demonstrate the feasibility and superiority of the proposed scheme on enhancing HVRT capability of DFIG-based wind farms.
出处 《CSEE Journal of Power and Energy Systems》 SCIE CSCD 2021年第4期698-707,共10页 中国电机工程学会电力与能源系统学报(英文)
基金 supported by the National Natural Science Foundation of China(No.51907134).
  • 相关文献

参考文献14

二级参考文献160

共引文献323

同被引文献48

引证文献6

二级引证文献17

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部