期刊文献+

110 kV及以上电压等级高压单芯交联聚乙烯电缆线路接地系统研究 被引量:3

Analysis for the Grounding System of 110 kV and the Above HV Single Core XLPE Cable
下载PDF
导出
摘要 高压单芯电缆在城市输电网中得到了越来越广泛的应用,但其接地系统发生异常时会产生高悬浮电压进而引发严重后果。在对电缆"导体芯-铝护套-石墨层-接地体"三级电容进行理论分析的基础上,按照单端接地系统和交叉互联接地系统两种工况,计算分析了由接地系统异常引起的电缆线路高悬浮电压,并通过案例进行实证,提出了解决电缆线路高悬浮电压的措施。 High voltage single core cable is more and more widely used in urban transmission network.However,when its grounding system is abnormal,it will produce high suspension voltage and lead to serious consequences.Based on the theoretical analysis of the three-level capacitance of the cable"conductor core-aluminum sheath-graphite layer-grounding body",according to the two working conditions of single-ended grounding system and cross-connected grounding system,the high suspension voltage of cable line caused by the abnormal grounding system is calculated and analyzed.Through case study,the measures to solve the problem of high suspension voltage of cable line are put forward.
作者 黄会贤 刘云龙 张午阳 黄华勇 HUANG Huixian;LIU Yunlong;ZHANG Wuyang;HUANG Huayong(State Grid Chongqing Power Supply Company,Chongqing 400100,China;State Grid Chongqing Jiangbei Power Supply Company,Chongqing 401147,China)
出处 《电工技术》 2021年第16期155-159,共5页 Electric Engineering
关键词 高压电缆 铝护套 悬浮电压 接地系统 high voltage cable aluminum sheath suspended potential grounding system
  • 相关文献

参考文献14

二级参考文献125

共引文献198

同被引文献19

引证文献3

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部