期刊文献+

隔离开关翻转机构万向节失效分析

Failure Analysis on Universal Joint of Turnover Device of Isolating Switch
下载PDF
导出
摘要 针对某750 kV变电站一隔离开关合闸操作时翻转机构万向节基座断裂问题,对断裂的万向节以及抽取同批次同型号万向节进行了分析,发现是由于万向节本身存在铸造缺陷造成的部件失效,建议优化生产工艺,并加强对入网金属铸件内部质量的检验和监督,加强设备运行和检修期间的巡视检查,以保证电网设备的安全稳定运行。 In view of the fracture of a universal joint pedestal of a turnover device of an isolating switch in a 750 kV Substation,tests and analyses are performed on the fractured universal joint and sampled spare joints of the same type and batch,based on which it is found that such failure is caused by inherent casting defects in universal joint.It is proposed to optimize its manufacturing process,and strengthen the inspection and supervision on the internal quality of such metal castings as well as inspections during operation and maintenance so as to ensure the safe and stable operation of equipment in power grid.
作者 滕玉林 李军 陈善义 谢金鹏 夏稀渊 TENG Yulin;LI Jun;CHEN Shanyi;XIE Jinpeng;XIA Xiyuan(Electric Power Research Institute of State Grid Gansu Electric Power Co.,Ltd.,Lanzhou 730070)
出处 《电力安全技术》 2021年第9期52-53,共2页 Electric Safety Technology
关键词 隔离开关 万向节 断裂 失效分析 isolating switch universal joint fracture failure analysis

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部