摘要
对阻容装置和避雷器的过电压抑制能力进行校核,进行变电站并联电抗器投切试验,将10kV阻容装置和氧化锌避雷器的操作过电压防护效果对比,还对四种不同过电压防护装置配置条件下的雷电过电压响应情况进行仿真计算,得出阻容装置和氧化锌避雷器配合使用能同时降低过电压波形幅值、陡度和频率的结论。
In this paper, the overvoltage suppression ability of the resistance-capacitance device and the arrester is checked, and the switching test of the shunt reactor in substations is carried out. The operating overvoltage protection effect of the resistance-capacitance device and the arrester is compared, the lightning overvoltage response of four different overvoltage protection devices is also simulated. It is concluded that the amplitude, steepness and frequency of the overvoltage waveform can be decreased by using the resistance-capacitance device together with metal oxide arrester.
作者
向缨竹
李欣
肖京
吴小忠
邓化龙
XIANG Yingzhu;LI Xin;XIAO Jing;WU Xiaozhong;DENG Hualong(State Grid Hunan Electric Power Company Limited Research Institute,Changsha 410007,China;State Grid Hunan Electric Power Company Limited,Changsha 410004,China;Hunan Changgao Senyuan Power Equipment Corporation L.imited,Hengyang 421007,China)
出处
《湖南电力》
2021年第5期7-13,21,共8页
Hunan Electric Power
基金
湖南省电力有限公司科技项目(5216A5200001)。
关键词
阻容装置
氧化锌避雷器
过电压抑制能力
overvoltage absorber
metal oxide arrester(MOA)
overvoltage suppression capability