期刊文献+

基于热环境评价指标的数据中心水冷空调热环境研究 被引量:1

Research on thermal environment of water-cooled air conditioning in data center based on thermal environment evaluation index
原文传递
导出
摘要 以数据中心水冷空调系统为研究对象,采用CFD软件模拟分析不同回风温度及服务器布局下的冷通道温度场、气流组织等,并选用热环境评价指标进行定量分析。结果表明,机房满负载时最佳回风温度为30℃,此时服务器无间隔的摆放方式热环境评价结果更优,且冷通道中间位置的气流组织较好。 Taking the data center water-cooled air-conditioning system as the research object, using CFD software to simulate and analyze the cold aisle temperature field and air distribution under different return air temperatures and server layouts, and select thermal environment evaluation indicators for quantitative analysis. The results show that the best return air temperature when the computer room is fully loaded is 30 ℃. At this time, the thermal environment evaluation result of the server without spacing is better, and the airflow organization in the middle of the cold aisle is better.
作者 杨帆 陈春良 杨欣 俞伟 孙元 吴卫东 YANG Fan;CHEN Chun-liang;YANG Xin;YU Wei;SUN Yuan;WU Wei-dong
出处 《节能》 2021年第9期72-76,共5页 Energy Conservation
关键词 水冷空调 服务器布局 气流组织 water-cooled air conditioner server layout air organization
  • 相关文献

参考文献2

二级参考文献25

  • 1石毅登,田怀璋,陈林辉,梁俊杰,伍志辉.采用变频技术的制冷装置的优势分析[J].制冷与空调,2004,4(5):59-62. 被引量:36
  • 2陈建东.中央空调系统水泵变频节能技术的应用分析[J].制冷技术,2006,26(4):12-14. 被引量:20
  • 3谢晓云,江亿,刘拴强,曲凯阳,于向阳.间接蒸发冷水机组设计开发及性能分析[J].暖通空调,2007,37(7):66-71. 被引量:44
  • 4GAO T Y, MILNES D, GEER J, et al. Experimental and numerical dynamic investigation of an energy efficient liquid cooled chillejrless data center test facility[J]. Energy and Buildings, 2015,47(3):83-96.
  • 5LU T, LU X S,REMES M,et al. Investigation of air management and energy performance in a data center in Finland : case study C J D- Energy and Buildings,2011,43(12) :3360-3372.
  • 6RATNESH S, CULLEN B. Dimensionless parameters for evaluation of thermal design and performance of large scale data centers [C] // 8th AIAA/ ASME Joint Thermophysics and Heat Transfer Conference,2002.
  • 7BASH C E, PATEL C D. Efficient thermal management of data centers-immediate and long-term research needs[J]. HVAC&-R Research,2003 ?9(2): 137-152.
  • 8Herrlin M K. Airflow and cooling performance of data centers : two performance metrics [ G ] // ASHRAE Trans,2008?114 (2):182-187.
  • 9HERRLIN M K. Rack cooling effectiveness in data centers and telecom central offices : the rack cooling index RCI[G] // ASHRAE Trans, 2005,111 (2): 1-11.
  • 10刘晓华,谢晓云,刘拴强,江亿.温湿度独立控制空调系统及其性能分析[J].中国建设信息(供热制冷),2008(7):22-26. 被引量:21

共引文献137

同被引文献7

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部