基于有载分接开关油室进行研发改造,搭建了短路燃弧试验平台并开展了16次短路燃弧试验,基于试验结果分析,提出压力释放阀投报警、油流继电器投跳闸的有载分接开关非电量保护装置标准化配置建议方案。
Based on the R&D and transformation of the oil compartment of the OLTC,a short-circuit arc test platform is built and 16 short-circuit arc tests are carried out.Based on the analysis of the test results,the on-load points for the pressure release valve to alarm and the oil flow relay to trip were proposed.Proposal for standardized configuration of non-electrical switch protection devices.
作者
徐海军
王进
廖文锋
陕华平
王佳妮
XU Hai-jun;WANG Jin;LIAO Wen-feng;SHAN Hua-ping;WANG Jia-ni(DC Technical Center of State Grid Corporation of China,Beijing 100052,China;North China Electric Power University,Beijing 102206,China)
出处
《变压器》
2021年第10期48-52,共5页
Transformer
基金
国家电网有限公司总部管理科技项目资助-国内外分接开关制造运行经验统计分析研究(项目编号:5500-202049355A-0-0-00)。