期刊文献+

电流互感器故障分析及诊断 被引量:5

Fault Analysis and Diagnosis on Current Transformer
下载PDF
导出
摘要 介绍了一起电流互感器故障的现场情况,分析诊断出了故障发生的原因为生产制造过程中,人工操作误差导致二次绕组间绝缘裕度过小,长时间运行后发生绝缘劣化击穿,并给出了预防此类故障的建议。 The field situation of a current transformer fault is introduced,and the causes of the fault are analyzed and diagnosed such that the insulation margin between the secondary windings is too small due to manual operation errors in the production and manufacturing process,and the insulation degradation breakdown might occur upon a long period of operation.Suggestions to prevent such faults are given so as to ensure the safe and stable operation of the substation.
作者 毕长生 刘利斌 李双胜 吴港 周明 袁超 岳重辰 BI Changsheng;LIU Libin;LI Shuangsheng;WU Gang;ZHOU Ming;YUAN Chao;YUE Zhongchen(Dalian Power Supply Company,Dalian 116000)
出处 《电力安全技术》 2021年第10期26-27,共2页 Electric Safety Technology
关键词 电流互感器 故障分析 故障诊断 差动保护 current transformer fault analysis fault diagnosis differential protection