严寒地区地铁车站环控系统运行性能实测研究 被引量:2

Field research on operating performance of underground railway station environmental control system in severe cold zone
下载PDF
导出
摘要 选取严寒地区的2座地铁车站,实地测试了全年不同季节车站环控系统的运行性能及取消轨底排风后轨行区的温度变化情况。结果显示:严寒地区地铁车站冬季站厅、站台温度保障效果不佳,需进一步降低冷风渗透的不利影响;列车活塞效应对车站影响显著,闭式运行及开式运行时出入口渗透新风量均可满足人员新风需求,考虑到公共区温度远低于设计规范要求,可关闭机械通风系统;列车停靠等对轨底温度的影响小于1℃,轨底排风的取消不会导致轨底温度过高。 Selects two underground railway stations in severe cold zone to measure the operating performance of the environmental control systems of the stations in different seasons throughout the year and the temperature change in the rail area without the exhaust fan at the rail bottom.The results show that the temperature of the hall and platform of underground railway stations in severe cold zone is lower than the design requirements in winter,and it is necessary to reduce the adverse effects of cold air penetration.The piston effect of trains has a significant impact on the station,and the penetration of outdoor air at the entrance and exit during closed operation and open operation can meet the outdoor air requirement of personnel.Considering that the temperature in the public area is far lower than the design specification requirements,the mechanical ventilation system can be turned off.The influence of train stop on the temperature of the rail bottom is less than 1℃,and the cancellation of rail bottom exhaust fan will not cause high rail bottom temperature.
作者 许峥浩 张涛 刘晓华 刘占英 张振义 李晨 Xu Zhenghao;Zhang Tao;Liu Xiaohua;Liu Zhanying;Zhang Zhenyi;Li Chen(Tsinghua University,Beijing,China;不详)
出处 《暖通空调》 2021年第11期89-94,共6页 Heating Ventilating & Air Conditioning
基金 国家重点研发计划项目(编号:2018YFC0705001) “严寒地区地铁车站环控系统运行性能研究”项目(编号:HGD-SJGL-D1D2-201048)。
关键词 严寒地区 地铁车站 环控系统 通风 热环境 性能实测 severe cold zone underground railway station environmental control system ventilation thermal environment performance measurement
  • 相关文献

参考文献6

二级参考文献22

共引文献69

同被引文献21

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部