期刊文献+

基于单端电压行波传输规律的柔直架空线路金属性接地故障测距方法 被引量:6

Metallic Grounding Fault Location Method for Flexible DC Overhead Lines Based on Single-terminal Voltage Traveling Wave Transmission Law
下载PDF
导出
摘要 为准确定位双极运行方式下高压柔性直流输电系统单极接地故障,提出一种基于正反向电压行波关系的单极接地故障测距原理及算法。研究了双极运行方式下发生单极接地故障时的边界条件以及故障后正向电压行波和反向电压行波的差模分量和地模分量之间的关系,在此基础上,提出了基于正反向电压行波关系的单极接地故障测距原理,并分析了过渡电阻对该故障测距原理的影响。仿真验证了所提故障测距原理的有效性和可靠性。 To accurately locate the unipolar grounding fault of a flexible high voltage direct current(HVDC)transmission system in bipolar operation mode,the principle for unipolar grounding fault location and the corresponding algorithm are proposed,which are based on the relationship between forward and reverse voltage travelling waves.The boundary conditions when a single-terminal grounding fault occurs in the bipolar operation mode are studied,together with the relationship between the differential-and ground-mode components of the forward and reverse voltage traveling waves after the fault.On this basis,the principle for unipolar grounding fault location based on the relationship between forward and reverse voltage travelling waves is put forward.In addition,the influence of transition resistance on the principle is also analyzed.Simulation results verify the validity and reliability of the proposed fault location principle.
作者 李博通 黄旭华 李春波 苏江 LI Botong;HUANG Xuhua;LI Chunbo;SU Jiang(Key Laboratory of Smart Grid of Ministry of Education,School of Electrical and Information Engineering,Tianjin University,Tianjin 300072,China)
出处 《电力系统及其自动化学报》 CSCD 北大核心 2021年第11期112-119,共8页 Proceedings of the CSU-EPSA
基金 国家自然科学基金联合基金资助项目(U1866205) 国家自然科学基金资助面上项目(51677125)。
关键词 高压柔性直流输电 双极运行方式 单极接地故障 故障测距 行波分析 high voltage direct current(HVDC)transmission bipolar operation mode unipolar grounding fault fault location traveling wave analysis
  • 相关文献

参考文献7

二级参考文献139

共引文献464

同被引文献65

引证文献6

二级引证文献7

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部