摘要
根据用于海拔2 500 m地区的2 400 kV直流电压发生器顶端均压罩和均压环的结构,有针对性地给出了电场强度控制值,使用有限元软件COMSOL对2 400 kV直流电压发生器的电场进行仿真和校验,发现顶端均压罩的最大场强是8.12 kV/cm,均压环的最大表面场强是9.58 kV/cm。为提高2 400 kV直流电压发生器的绝缘性能,有必要对均压环进行结构优化,在多次尝试后,增加了表面场强较大的几个均压环的曲率半径,并调整了均压环的位置。经过优化后,均压环的最大表面场强降低至8.12 kV/cm,降低约15.2%,提高了2 400 kV直流电压发生器的绝缘性能。
According to the structures of both grading shield and grading ring on top of 2 400 k V DC voltage generator for the areas at altitude of 2 500 m,the control value of electric field intensity is specifically given. The finite element software COMSOL is used to simulate and calibrate the electric field of 2 400 k V DC voltage generator,finding that the maximum electric field intensity of the grading shield on the top is8.12 kV/cm,and the maximum surface electric field intensity of the grading ring is 9.58 kV/cm. In order to improve the insulation performance of the 2 400 kV DC voltage generator,it is necessary to optimize the structure of the grading ring. After many attempts,the curvature radius of several grading rings with large surface electric field intensity is increased and positions of grading rings are adjusted. After optimization,the maximum surface electric field intensity of the grading ring is reduced to 8.12 kV/cm,a reduction of about 15.2%,and the insulation performance of the 2 400 kV DC voltage generator has been improved.
作者
王生富
苟廷韬
邓辉
蒋玲
包正红
于鑫龙
张仲秋
胡梦晨
WANG Shengfu;GOU Tingtao;DENG Hui;JIANG Ling;BAO Zhenghong;YU Xinlong;ZHANG Zhongqiu;HU Mengchen(Electric Power Research Institute of State Grid Qinghai Electric Power Company,Xining 810008,China;Mianzhu Xinan Electrotechnical Equipment Co.,Ltd.,Sichuang Mianzhu 618200,China)
出处
《电力电容器与无功补偿》
2021年第6期203-210,共8页
Power Capacitor & Reactive Power Compensation
基金
国家电网公司总部科技项目(高海拔地区盐湖等特殊地理环境下输电线路外绝缘特性研究)。
关键词
2400
kV直流电压发生器
电场校验
均压环
结构优化
2400 kV DC voltage generator
electric field intensity check
grading ring
structure optimization