期刊文献+

一起500 kV变压器运行异常处置与分析

Abnormality Analysis of a 500 kV Transformer Fault
下载PDF
导出
摘要 文章介绍了一起500 kV变压器因高压侧固定引线升高座绝缘隔板未安装,导致高压引出线区域均压球上、下沿对应的内绝缘纸筒内异常放电的事件,并结合事故现象和诊断试验结果进行异常处置,并制定相应的排查整改措施。 This paper introduces an abnormal discharge of a 500 kV transformer in the inner insulating paper cylinder corresponding to the upper and lower edges of the voltage equalizing ball in the high voltage outgoing line area due to the non-installation of the insulating partition of the elevated base of the high voltage outgoing line.Combined with the abnormal phenomenon and results of diagnosis experimentation,abnormality is handled and rectification measures are put forward.
作者 王鹏辉 郑晓琼 严太山 杨乃旗 李永熙 WANG Penghui;ZHENG Xiaoqiong;YAN Taishan;YANG Naiqi;LI Yongxi(Anhui Bright Property Development Co.,Ltd.,Hefei 230022,China;State Grid Anhui Ultra High Voltage Company,Hefei 230022,China)
出处 《安徽电气工程职业技术学院学报》 2021年第4期46-51,共6页 Journal of Anhui Electrical Engineering Professional Technique College
关键词 变压器 放电 诊断试验 异常处置 transformer discharge diagnosis experimentation abnormality handling