期刊文献+

220kV主变压器比率差动保护误动作分析 被引量:1

Analysis of Misoperation of 220 kV Main Transformer Ratio Differential Protection
下载PDF
导出
摘要 针对一起线路单相短路后主变压器比率差动保护误动作故障,从主变压器差动保护定值、动作逻辑和告警信号等方面进行分析,认为主变压器CPU1的AD芯片内部回路损坏是导致保护误动作的原因,提出主变压器保护装置增加零漂越限告警等功能,以提升电流采样满偏的灵敏性,保障主变压器比率差动保护的可靠动作。 In view of the malfunction of the ratio differential protection of the main transformer after a single-phase short circuit of the line,the analysis is carried out from the aspects of the differential protection setting,operation logic and alarm signal of the main transformer.It is considered that the damage of the internal circuit of the AD chip of the main transformer CPU1 is the cause of portection misoperation.We propose the main transformer protection device adds functions such as zero drift over-limit alarm to improve the sensitivity of the current sampling full deviation and ensure the reliable action of the main transformer ratio differential protection.
作者 陈天英 李铁成 侯仰军 李泽 陈铄鑫 CHEN Tianying;LI Tiecheng;HOU Yangjun;LI Ze;CHEN Shuoxin(State Grid Hebei Electric Power Co..Ltd.Electric Power Research Institute,Shijiazhuang 050021,China;Hebei Huadian Shijiazhuang Thermal Power Co..Ltd..Shijiazhuang 050021,China;Hcbti Huarui Energy Group Co.,Ltd.,Shijiazhuang 050021,China)
出处 《河北电力技术》 2021年第6期42-44,共3页 Hebei Electric Power
基金 国网河北省电力有限公司科技项目(kj2020-048)。
关键词 变压器 比率差动 AD芯片 继电保护 transformer ratio differential AD chip relay protection
  • 相关文献

参考文献2

二级参考文献3

共引文献8

同被引文献5

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部